WARRANTYIntek, Inc. warrants each Rheotherm product to be free from defectsin material and workmanship under normal use and service, Intek'soblig
- 8 -3.3 ADJUSTING THE TRIP POINTAdjust the flow switch trip level as follows:1. Establish a flow rate at the desired trip level. (This should be don
- 9 -2. The transducer isolation check is performed as follows (see Figure B):A. Disconnect the transducer cable from the electronics.B. Make the circ
- 10 -SECTION 4 ! MAINTENANCE4.1 GENERAL MAINTENANCECertain precautions should be taken to insure proper performance of all models of flow instruments
- 11 -4.3 TROUBLE SHOOTINGTABLE I. TROUBLE SHOOTING GUIDEOBSERVATION PROBABLE CAUSE REMEDYFlow trip level continuallydrifting downward with constantfl
- 12 -SECTION 5 ! CUSTOMER SERVICEIntek's corporate philosophy is to solve our customer's difficult flow measurement problems. Thismeans t
- 13 -SECTION 6 ! CUSTOM INFORMATION6.1 UNIT IDENTIFICATIONModel no.:Serial no.: Customer identification:6.2 CONFIGURATIONThe configuration of this u
~---i I ' i i ' ' i :;:=-0-_:;..!~· \ ~~,_-: ---~ -·----> L() I 0 L 0 <( E 0 C\J I ~ I FIGURE 1. Rheotherm 100 Rev. B Signal Con
TABLE OF CONTENTSSECTION 1 ! GENERAL INFORMATION ... - 1 -1.1 INTRODUCTION ...
- 1 -SECTION 1 ! GENERAL INFORMATION1.1 INTRODUCTIONRheotherm flow switches offer reliable flow switch protection in liquids, gases and slurries. The
- 2 -Nonintrusive transducer(TU)Example of dual probewith flange fittingExample of single probewith NPT fitting1.2 DESCRIPTION OF OPERATIONRheotherm f
- 3 -5. Keep transducer wetted surfaces clean and free of permanent layer build-up.6. Do not exceed pressure limits of the tube or fittings.7. Maintai
- 4 -SECTION 2 ! INSTALLATION2.1 TRANSDUCER. IMPORTANT: All transducers have a directional arrow on the tagand/or etched into a metal part. Before in
- 5 -Some TU transducers have an integrally mounted cable; do not pull on this cable, or attemptto remove the fitting where the cable enters the shell
- 6 -1. NEMA 4 The standard industrial housing, this enclosure is watertight (non-submersible)when the door is properly clamped shut. The housing
- 7 -SECTION 3 ! OPERATION3.1 START UPTypically, Rheotherm flow switches come from the factory set up for a 10 to 1 flow rate range, and withthe trip